PLB-12/24 SF6 load break switch is a HV electrical equipment of high reliability and maintenance-free, with rated voltage 12kV/24kV and rated frequency 50Hz, applicable for 10kV distribution line as load regulation & control as well as distribution automation system. There are two types for the product: manual and motor-driven type.
	 
Technical Parameter
| Item | Unit | Data | |||||
| 12kV | 24kV | 36kV | |||||
| Rated Current | A | 630 | 630 | 630 | |||
| Rated Voltage | kV | 12 | 24 | 26 | |||
| Rated Insulation Level | 1 min Power Frequency Withstand Voltage | Dry) | 42/49 | 50/65 | 70/90 | ||
| Wet | 34 | 55 | 65 | ||||
| Lightning Impulse Withstand Voltage (Peak) | 75/85 | 125/145 | 150/175 | ||||
| Rated Frequency | Hz | 50/60 | 50/60 | 50/60 | |||
| Rated Short-circuit Closing Current (Peak) | kA | 50 | 63 | 63 | |||
| Rated Short-time Withstand Voltage (4s) | 20 | 25 | 25 | ||||
| Rated Peak Withstand Current | 50 | 63 | 63 | ||||
| Rated Operating Voltage (Controller) | V | AC220 | AC220 | AC220 | |||
| Auxiliary Circuit Rated Voltage | DC24 | DC24 | DC24 | ||||
| Mechanical Life | times | 3000 | 5000 | 5000 | |||
| SF6 Rated Air Pressure (20°C) | MPa | ≤0.71 | ≤0.71 | ≤0.71 | |||
| SF6 Rated Annual Leak Rate | % | ≤0.5 | |||||
| Operation Mode | 
 | Spring Operation (Manual/Electric) | |||||